gas cabinet current Sensor
+
  • gas cabinet current Sensor
Product Overview

The LZM-10E gas cabinet current sensor is designed and manufactured in accordance with the technical specifications of the State Grid Corporation's primary and secondary integration equipment and the group standard T/CES 018-2019 "Technical Conditions for 10kV and 20kV AC Sensors in Distribution Networks". The sensor can simultaneously output phase current and zero-sequence current sampling signals, can be used with environmentally friendly gas cabinets, and features low power consumption, high accuracy, and the three-in-one characteristics of measurement, metering, and protection.

 

Implementation Standards

T/CES 018-2019

 

Technical Parameters

Voltage Section

ParameterValue
Rated Voltage● Phase Current: 600a/1V 
● Zero-sequence Current: 20a/0.2V
Accuracy Class● Phase Current: Protection 5P20, Metering/Measurement 0.5S 
● Zero-sequence Current: Class 1S (1%~120%), Protection 10P20
PolarityReduced Polarity
Rated Load20kΩ
Operating Frequency50±2.5hz
Temperature Range-40℃~70℃
Secondary Power Frequency Withstand VoltageSecondary terminal to ground power frequency withstand voltage 1 kV (1min)
Primary Power Frequency Withstand Voltage42kV (1min)
Impulse Voltage75kV

 

Dimensions

Keywords

gas cabinet current Sensor
+
  • gas cabinet current Sensor

gas cabinet current Sensor

The LZM-10E gas cabinet current sensor conforms to the technical specifications of the State Grid Corporation's primary and secondary integration equipment and is designed and manufactured in accordance with the group standard T/CES 018-2019 "Technical Conditions for 10kV and 20kV AC Sensors in Distribution Networks". The sensor can simultaneously output phase current and zero-sequence current sampling signals, can be used with environmentally friendly gas cabinets, and features low power consumption, high accuracy, and a three-in-one design for measurement, metering, and protection.


Product Overview

The LZM-10E gas cabinet current sensor is designed and manufactured in accordance with the technical specifications of the State Grid Corporation's primary and secondary integration equipment and the group standard T/CES 018-2019 "Technical Conditions for 10kV and 20kV AC Sensors in Distribution Networks". The sensor can simultaneously output phase current and zero-sequence current sampling signals, can be used with environmentally friendly gas cabinets, and features low power consumption, high accuracy, and the three-in-one characteristics of measurement, metering, and protection.

 

Implementation Standards

T/CES 018-2019

 

Technical Parameters

Voltage Section

ParameterValue
Rated Voltage● Phase Current: 600a/1V 
● Zero-sequence Current: 20a/0.2V
Accuracy Class● Phase Current: Protection 5P20, Metering/Measurement 0.5S 
● Zero-sequence Current: Class 1S (1%~120%), Protection 10P20
PolarityReduced Polarity
Rated Load20kΩ
Operating Frequency50±2.5hz
Temperature Range-40℃~70℃
Secondary Power Frequency Withstand VoltageSecondary terminal to ground power frequency withstand voltage 1 kV (1min)
Primary Power Frequency Withstand Voltage42kV (1min)
Impulse Voltage75kV

 

Dimensions

Get a Quote